5925-01-309-7356 CIRCUIT BREAKER Index 5925-01-309-7358 CIRCUIT BREAKER

National Stock Number:
5925-01-309-7357

Federal Supply Class:
5925

National Item Identification Number:
013097357

Description:
CIRCUIT BREAKER

Detail:
A DEVICE WITH MEANS OTHER THAN FUSES FOR AUTOMATICALLY OPENING THE CIRCUIT IN WHICH IT IS INSTALLED WHEN THE CURRENT VARIES FROM THE PREDETERMINED VALUE FOR WHICH THE DEVICE IS SET. MAY INCLUDE PROVISIONS FOR MANUAL OPERATION. AT LEAST ONE SET OF CONTACTS MUST BE IN SERIES WITH THE ACTUATING ELEMENT(S). A COMBINATION OF SEMICONDUCTOR AND PASSIVE DEVICES MAY BE USED IN LIEU OF CONTACTS. FOR AUTOMATICALLY OPERATED ITEMS IN WHICH THE ACTUATING (TRIPPING) ELEMENT AND CONTACTS ARE NOT IN SERIES, SEE RELAY (AS MODIFIED). FOR ITEMS WHICH ARE OPERATED BOTH MANUALLY AND AUTOMATICALLY BUT THE ACTUATING ELEMENTS AND CONTACT ARE NOT IN SERIES, SEE RELAY-SWITCH. EXCLUDES CIRCUIT BREAKER BOX AND MAGNETO "BREAKER" ASSEMBLIES. SEE ALSO SWITCH (AS MODIFIED); AND CONTROLLER.


Manufacturer Information:
M55629/22PRPRPR81349MILITARY SPECIFICATIONS PROMULGATED BY MILITARY DEPARTMENTS/AGENCIES UNDER AUTHORITY OF DEFENSE STANDARDIZATION MANUAL 4120 3-M
MIL-C-55629/2281349MILITARY SPECIFICATIONS PROMULGATED BY MILITARY DEPARTMENTS/AGENCIES UNDER AUTHORITY OF DEFENSE STANDARDIZATION MANUAL 4120 3-M
MIL-PRF-55629/2281349MILITARY SPECIFICATIONS PROMULGATED BY MILITARY DEPARTMENTS/AGENCIES UNDER AUTHORITY OF DEFENSE STANDARDIZATION MANUAL 4120 3-M


Techincal Specification:
POLE QUANTITY3
MAXIMUM CONTINUOUS LOAD CURRENT RATING PER POLE12.5 AMPERES AC ALL LOCATIONS
CIRCUIT PROTECTION TYPEOVERCURRENT ALL LOCATIONS
TERMINAL TYPE AND QUANTITY6 SCREW
OPERATING VOLTAGE TYPE AND RATING PER POLE IN VOLTS240.0 AC ALL LOCATIONS
TRIP RELEASE CHARACTERISTICTIME DELAY AND
INSTANTANEOUS ALL LOCATIONS
RESET METHODMANUAL
BODY STYLEMULTIPOLE-SINGLE ACTUATOR TYPE
MOUNTING FACILITY TYPE AND QUANTITY3 THREADED HOLE
TRIP RELEASE METHODMAGNETIC ALL LOCATIONS
FREQUENCY IN HERTZ400.0 ALL LOCATIONS
MAXIMUM INTERRUPTING CAPACITY CURRENT TYPE AND RATING PER POLE IN AMPS1000.0 AC ALL LOCATIONS
INTERNAL TRIP RELEASE CONFIGURATIONSERIES TRIP ALL LOCATIONS
TRIP DELAY TIME IN SECONDS PER RATED CONTINUOUS CURRENT0.600 MINIMUM AT 150 PCT AND
5.800 MAXIMUM AT 150 PCT ALL LOCATIONS
ULTIMATE TRIP RATING OF CONTINUOUS CURRENT RATING PER POLE IN PERCENT150.0 ALL LOCATIONS
MAIN CONTACT TRIPPING MECHANISM TYPETRIP FREE
BODY LENGTH2.265 INCHES MAXIMUM
BODY WIDTH2.000 INCHES NOMINAL
CENTER TO CENTER DISTANCE BETWEEN TERMINALS PARALLEL TO LENGTH0.750 INCHES NOMINAL
CENTER TO CENTER DISTANCE BETWEEN TERMINALS PARALLEL TO WIDTH1.530 INCHES NOMINAL
MOUNTING SURFACE TO TERMINAL END DISTANCE2.102 INCHES MAXIMUM
THREAD SERIES DESIGNATORUNC
NOMINAL THREAD SIZE0.138 INCHES
MANUAL ACTUATOR TYPE AND QUANTITY1 TOGGLE
ACTUATOR FUNCTIONRESET
AUXILIARY SWITCH FUNCTION AND QUANTITY3 CONTROL
SWITCH TERMINAL TYPETAB, SOLDER LUG
FEATURES PROVIDEDHIGH INRUSH PROTECTION
SPECIAL FEATURESWITH AUXILLIARY CONTACTS
SPEC/STD CONTROLLING DATA
MANUFACTURERS CODE81349
NON-DEFINITIVE GOVERNMENT SPEC/STD REFERENCEMIL-PRF-55629/22
DEFINITIVE GOVERNMENT SPEC/STD REFERENCEM55629/22PRPRPR


Click here to Register for Free 30-day Trial