POLE QUANTITY | 2 |
MAXIMUM CONTINUOUS LOAD CURRENT RATING PER POLE | 1.750 AMPERES AC ALL LOCATIONS |
CIRCUIT PROTECTION TYPE | OVERCURRENT ALL LOCATIONS |
TERMINAL TYPE AND QUANTITY | 4 SCREW |
OPERATING VOLTAGE TYPE AND RATING PER POLE IN VOLTS | 240.0 AC ALL LOCATIONS |
TRIP RELEASE CHARACTERISTIC | INSTANTANEOUS AND |
| TIME DELAY ALL LOCATIONS |
RESET METHOD | MANUAL |
BODY STYLE | MULTIPOLE-SINGLE ACTUATOR TYPE |
MOUNTING FACILITY TYPE AND QUANTITY | 2 THREADED HOLE |
TRIP RELEASE METHOD | MAGNETIC ALL LOCATIONS |
FREQUENCY IN HERTZ | 400.0 ALL LOCATIONS |
MAXIMUM INTERRUPTING CAPACITY CURRENT TYPE AND RATING PER POLE IN AMPS | 1000.0 AC ALL LOCATIONS |
INTERNAL TRIP RELEASE CONFIGURATION | SERIES TRIP ALL LOCATIONS |
TRIP DELAY TIME IN SECONDS PER RATED CONTINUOUS CURRENT | 0.600 MINIMUM AT 150 PCT AND |
| 5.800 MAXIMUM AT 150 PCT ALL LOCATIONS |
ULTIMATE TRIP RATING OF CONTINUOUS CURRENT RATING PER POLE IN PERCENT | 150.0 ALL LOCATIONS |
MAIN CONTACT TRIPPING MECHANISM TYPE | TRIP FREE |
BODY LENGTH | 2.000 INCHES NOMINAL |
BODY WIDTH | 1.515 INCHES MAXIMUM |
CENTER TO CENTER DISTANCE BETWEEN TERMINALS PARALLEL TO LENGTH | 1.530 INCHES NOMINAL |
CENTER TO CENTER DISTANCE BETWEEN TERMINALS PARALLEL TO WIDTH | 0.750 INCHES NOMINAL |
MOUNTING SURFACE TO TERMINAL END DISTANCE | 2.232 INCHES MAXIMUM |
THREAD SERIES DESIGNATOR | UNC |
NOMINAL THREAD SIZE | 0.138 INCHES |
MANUAL ACTUATOR TYPE AND QUANTITY | 1 TOGGLE |
ACTUATOR FUNCTION | RESET |
AUXILIARY SWITCH FUNCTION AND QUANTITY | 3 CONTROL |
SWITCH TERMINAL TYPE | TAB, SOLDER LUG |
FEATURES PROVIDED | HIGH INRUSH PROTECTION |
SPECIAL FEATURES | WITH AUXILLIARY CONTACTS |
SPEC/STD CONTROLLING DATA | |
NON-DEFINITIVE GOVERNMENT SPEC/STD REFERENCE | MIL-PRF-55629/21 |
MANUFACTURERS CODE | 81349 |
DEFINITIVE GOVERNMENT SPEC/STD REFERENCE | M55629/21GRGR |